Enter readings below — each check verdicts itself as you go
Work safe. Isolate and lock off before touching terminals. Discharge capacitors (across a resistor) and test them out of circuit.
Capacitorskip if not testing one
Amps vs nameplateclamp meter, running
3-phase voltage balance3-phase only
3-phase current balance3-phase only
How these checks work
Capacitor: capacitors must measure within the tolerance printed on their label — commonly ±5–6% for run caps and ±10–25% for start caps. Weak caps cause hard starts and high running amps; near-zero µF is a dead cap.
Amps: running current is compared numerically with entered RLA/FLA and LRA. These ratios do not prove overload, locked rotor or low charge. Use compressor MCC, manufacturer performance data, load/modulation and confirmed motor state.
Voltage imbalance (NEMA method: max deviation from the average of the three line-to-line voltages) uses 1% as a screening reference. Above 1%, check manufacturer limits and derating. Do not operate at severe imbalance without correcting the supply and following OEM instructions.
Current imbalance over ~10% points at windings, connections or supply; severe imbalance usually means a lost phase.
Diagnostic guide only — compare to the nameplate and your own judgement.